Underground Water Mains Leak Detection in Sheffield

A underground mains leak in Sheffield was located using flow metering, acoustic correlation, tracer gas, and pressure testing as part of water mains leak detection that identified two separate faults on the external supply at a property in S9. The work was carried out by engineer Brett Steele.

Leak Located Sheffield 0800 731 3843
CIPHE CIPHE accredited
WIAPS WIAPS member
£5m public liability insurance

THE UK'S #1 LEAK DETECTION SPECIALISTS

Facts

LocationSheffield
CountySouth Yorkshire
Leak TypeWater Mains Leak Detection
Property TypeResidential property
Detection MethodFlow Metering, Acoustic Correlation, Tracer Gas, Pressure Testing
OutcomeTwo leaks found and repaired on external mains supply.

Symptoms

water meter and stopwatch showing 1 litre flow rate during leak detection

A property in S9 was experiencing elevated water consumption, prompting suspicion of a leak on the underground supply. A meter was located on the public footpath at the driveway entrance, with an internal stopcock accessible in the basement.

Initial testing with the internal stopcock turned on for half an hour showed consistent meter usage, pointing to an active leak on the external supply pipe between the meter and the building.

The concern was that an uncontrolled loss of this kind, if left unaddressed, would continue to drive up consumption with no visible signs above ground. Water mains leak detection was required to identify the precise source before any excavation could be justified.

With the external supply running unseen beneath a front garden and driveway, pinpointing the fault without disruptive guesswork required specialist equipment and a structured approach.

Key Symptom
With the internal stopcock isolated, the meter showed consistent usage — recording approximately one litre in just over 30 seconds — confirming an active leak on the external supply.

Methods Used

tracer gas probe placed in front garden soil during leak detection survey

The investigation began by confirming the leak was external using flow metering at the street meter, with the internal stopcock isolated. Acoustic profiling was then carried out, which raised a concern in the vicinity of the internal stopcock.

To narrow the location further, tracer gas was purged into the pipework and a full sweep of the site was conducted using a specialist gas analyser, identifying a zone of high gas emission in the front garden close to the edge of the driveway.

A trial excavation in the grassed area exposed the mains supply and revealed a leak at a transition fitting where the 25mm MDPE reduced to 15mm copper. After reseating and tightening that fitting, a pressure test indicated further loss.

The MDPE pipe was then tracked under the driveway, where a secondary leak — a small crack in the pipe — was located and repaired. This kind of layered approach is typical of water mains leak detection where multiple faults can exist on a single supply run.

Flow Metering. Used at the street meter with the internal stopcock isolated to confirm active external leakage and quantify the flow rate at approximately one litre per 30 seconds.

Acoustic Correlation. Applied across the supply route to profile noise patterns, raising a specific concern close to the internal stopcock and guiding the initial focus area.

Tracer Gas. Purged into the pressurised pipework and detected at surface level using a specialist gas analyser, identifying high readings in the front garden close to the driveway edge.

Pressure Testing. Carried out after each repair stage to verify whether loss had been eliminated, confirming a second fault remained after the first fitting was addressed, and ultimately proving supply integrity once both repairs were complete.

Investigation Process

  1. 1
    Meter test with stopcock isolated

    With the internal stopcock turned off, the street meter was monitored and showed consistent usage at approximately one litre in just over 30 seconds, confirming the leak was on the external supply.

  2. 2
    Acoustic profiling conducted

    Acoustic equipment was deployed across the supply route. A notable concern was raised in the area close to the internal stopcock.

  3. 3
    Tracer gas introduced and site swept

    Tracer gas was purged into the pipework and a full sweep of the property was carried out with a specialist gas analyser. High readings were detected in the front garden, close to the edge of the driveway.

  4. 4
    Trial excavation in grassed area

    An excavation was made in the grassed area of the front garden, exposing the mains supply and revealing a leaking transition fitting where the 25mm MDPE pipe reduced to 15mm copper.

  5. 5
    First fitting reseated and pressure tested

    The transition fitting was reseated and tightened. A subsequent pressure test showed further pressure loss, indicating an additional fault remained on the supply.

  6. 6
    Secondary leak located under driveway

    The MDPE pipe was tracked under the driveway where a small crack in the pipe was identified as the source of the secondary leak.

  7. 7
    Cracked section removed and repaired

    The cracked section of MDPE pipe was removed and repaired using a 25mm MDPE coupler.

  8. 8
    Final pressure test confirms integrity

    A final pressure test recorded no further loss, and no uncontrolled usage was present at the meter, confirming the supply was fully restored.

Result & Outcome

leak located at cracked 25mm MDPE supply pipe exposed beneath driveway

Two separate faults were identified and repaired on the external mains supply at the property in S9. The first was a leaking transition fitting where 25mm MDPE reduced to 15mm copper, located in the front garden close to the driveway edge. The second was a cracked section of 25mm MDPE pipe running beneath the driveway itself. Both were confirmed through staged pressure testing, which showed remaining loss after the first repair and a clean result only once the second repair was complete.

The cracked pipe section was removed and replaced using a 25mm MDPE coupler. With no further pressure loss recorded and no uncontrolled usage visible at the street meter, the integrity of the supply was confirmed. This is the standard of proof required to close a water mains leak detection case — zero movement on the meter under controlled conditions.

The engineer has recommended that soft sand be used to bed the pipe before backfilling the excavations, protecting the repaired MDPE from damage during reinstatement.

Completed by Brett Steele, leak detection engineer at ADI Leak Detection.

Suspect a leak at your property?

ADI Leak Detection specialists investigate leaks like this across the UK every day. No find, no fee terms apply on qualifying jobs.