Internal Cold Mains Leak Detection in Northampton

An internal cold mains leak in Northampton was located using pressure testing, acoustic listening, a damp meter, and visual inspection, with water mains leak detection confirming the fault beneath the bathroom floor at a property in NN16. The work was carried out by engineer Scott Hardcastle.

Leak Located Northampton 0800 731 3843
CIPHE CIPHE accredited
WIAPS WIAPS member
£5m public liability insurance

THE UK'S #1 LEAK DETECTION SPECIALISTS

Facts

LocationNorthampton
CountyNorthamptonshire
Leak TypeWater Mains Leak Detection
Property TypeResidential property
Detection MethodPressure Testing, Acoustic Listening, Damp Meter, Visual Inspection
OutcomeLeaking push-fit coupling found under bathroom floor, repaired.

Symptoms

damp meter reading at bathroom floor edge during leak detection

The property in NN16 is a bungalow where the water company had confirmed a loss of approximately 3 litres per hour. Despite several visits from other companies, the source of the leak had not been found, though a previous contractor had established that the leak was internal rather than on the external supply.

The customer was left with an unresolved loss and no clear path to a repair.

With the property served by a combi boiler and system pressure holding steady, there were no obvious visible signs to guide the investigation. Internal leak detection was needed to pinpoint the exact location without unnecessary disruption to the property.

Key Symptom
A pressure test showed a small drop on the hot feed, and a hissing sound was audible beneath the bathroom floor under the basin.

Methods Used

leak located at unprotected push-fit couplings embedded in screed beneath bathroom floor tiles

A visual inspection of the property was carried out first, during which a faint hissing noise was identified in the bathroom and traced to the area beneath the floor under the basin. A pressure test was then performed, confirming a drop on the hot feed and narrowing the search to that zone.

Acoustic listening equipment and a damp meter were deployed to confirm the precise location of the leak without lifting the floor unnecessarily.

This is the methodical approach that internal leak detection requires — working from audible and pressure indicators down to a confirmed point before any floor tiles are removed. The process avoided unnecessary disruption and allowed the repair to be targeted to a single small area.

Pressure Testing. A pressure test was applied to the system and showed a measurable drop on the hot feed, confirming an active leak and identifying which circuit was affected.

Acoustic Listening. Acoustic equipment was used to detect and trace the hissing sound beneath the bathroom floor, helping confirm the leak position under the basin before any tiles were lifted.

Damp Meter. A damp meter was used alongside the acoustic equipment to corroborate the leak location beneath the tiled floor under the basin.

Visual Inspection. An initial walk-through of the property identified the bathroom as the area of interest and picked up the audible hissing that directed the investigation.

Investigation Process

  1. 1
    Visual Inspection and Sound Identification

    A visual inspection of the property was carried out. A slight hissing noise was heard in the bathroom and traced to the area beneath the floor under the basin.

  2. 2
    Pressure Test

    A pressure test was completed on the system. A small but measurable drop was recorded on the hot feed, confirming an active leak on that circuit.

  3. 3
    Acoustic and Damp Meter Survey

    Acoustic listening equipment and a damp meter were used to confirm the leak location beneath the tiled floor under the basin, before any floor coverings were disturbed.

  4. 4
    Tile Removal and Inspection

    Two tiles were lifted to expose the area. The concrete was found to have been laid directly over plastic pipework with no protective sleeving or ducting in place.

  5. 5
    Fault Identified

    A push-fit coupling was found to be leaking and was barely attached to the pipe. This was the source of the confirmed water loss.

  6. 6
    Repair Carried Out

    The damaged section of pipe was removed and replaced with a new piece of 22mm copper pipe, fitted securely to resolve the fault.

  7. 7
    Retest and Sign-Off

    The system was pressure tested again following the repair and held successfully. The basin was refitted before leaving the property.

Result & Outcome

fault identified at heavily corroded section of copper pipe removed from beneath bathroom floor — leak located at

The leak was confirmed beneath the bathroom floor under the basin, originating from a push-fit coupling that was barely attached to the plastic pipework. Two tiles were removed to access the fault — no wider disruption to the property was required. The damaged section was cut out and replaced with a new piece of 22mm copper pipe, and a follow-up pressure test confirmed the repair was sound.

For a property in NN16 where multiple previous visits had failed to resolve the issue, this internal leak detection result gave the customer a clear answer and a completed repair in a single visit. The basin was refitted before the engineer left.

One concern remains: the plastic pipework and fittings beneath the bathroom floor have been screeded over without any protective sleeving. This creates a risk of further leaks in the same area over time. Rerouting the pipework from the loft space is strongly recommended to avoid a repeat of the same problem.

Completed by Scott Hardcastle, leak detection engineer at ADI Leak Detection.