Underground Water Mains Leak Detection in Chatteris
A underground mains leak in Chatteris was located using tracer gas, pressure testing, and visual inspection as part of water mains leak detection carried out on the existing pipework. Found by engineer Scott Hardcastle.
Facts
| Location | Chatteris |
|---|---|
| County | Cambridgeshire |
| Leak Type | Water Mains Leak Detection |
| Property Type | Residential property |
| Detection Method | Tracer Gas, Pressure Testing, Visual Inspection |
| Outcome | Underground mains leak located at front of property, repaired. |
Symptoms
To confirm the source, both stopcocks were checked — the main residence stopcock and the separate garage stopcock. With both closed, the external water meter continued to show movement, isolating the leak to the section of pipework between the meter and the stopcocks.
This is a reliable indicator in water mains leak detection: if the meter runs with all internal isolation confirmed, the loss is external and underground.
Methods Used
Gas was detected bubbling up through the soil at the front of the property, giving a precise location before any excavation began. Pressure testing supported the isolation confirmation already established through the stopcock checks.
Visual inspection was carried out once the excavation exposed the pipework.
Tracer Gas. Introduced into the cold main pipework via the garage connection; the gas escaped through the leak and was detected bubbling at the soil surface at the front of the property, pinpointing the exact excavation point.
Pressure Testing. Used to confirm the isolation findings from the stopcock checks, verifying that movement on the external meter was attributable to a loss on the buried mains section.
Visual Inspection. Carried out on the exposed fitting once the excavation was complete, identifying the loose compression nut, the split olive, and the use of an inappropriate fitting on the mains pipework.
Investigation Process
-
1Stopcocks isolated and meter checked
Both the main residence stopcock and the garage stopcock were turned off. The external water meter continued to show movement, confirming the leak was on the external mains between the meter and the stopcocks.
-
2Mains isolated at meter, tracer gas introduced
The mains supply was turned off at the meter. Tracer gas was connected into the cold main pipework via the garage, with the pipe pressurised with gas to locate the escape point.
-
3Gas detected at the front of the property
Tracer gas was quickly detected bubbling out of the soil at the front of the property, identifying a precise location for excavation.
-
4Excavation carried out
With the customer's assistance, a large hole was dug at the indicated location, exposing the buried pipework at the leak point.
-
5Defective fitting identified
A brass 22mm compression tee wrapped in Denso tape was found. One compression nut was loose and the olive was split — the fitting was not appropriate for use on mains pipework.
-
6Correct fitting sourced and installed
An appropriate replacement fitting was purchased from the merchants. The tee was replaced, and the garage pipework was reconnected.
-
7System tested and confirmed clear
The system was tested after the repair, with no further movement detected on the external water meter.
Result & Outcome
The customer has been advised that other inappropriate fittings may remain elsewhere on the pipework, given the nature of what was found. The customer is considering having the supply replaced with new MDPE pipe in the future, which would remove the risk posed by any remaining unsuitable fittings on the existing mains.