Underground Water Mains Leak Detection in Banbury

A underground mains leak in Banbury was located using sectional isolation, tracer gas, acoustic listening, and pressure testing as part of a thorough water mains leak detection investigation on a buried supply pipe. The work was carried out by engineer Vincent Morgan.

Leak Located Banbury 0800 731 3843
CIPHE CIPHE accredited
WIAPS WIAPS member
£5m public liability insurance

THE UK'S #1 LEAK DETECTION SPECIALISTS

Facts

LocationBanbury
CountyOxfordshire
Leak TypeWater Mains Leak Detection
Property TypeResidential property
Detection MethodSectional Isolation, Tracer Gas, Acoustic Listening, Pressure Testing
OutcomeLeak found at transition joint beneath side pathway, joint replaced.

Symptoms

external water meter cover on driveway at initial inspection before leak detection works

The meter was registering flow at a rate of 1 litre per minute with all internal fittings off. Underground leaks of this type can persist undetected for extended periods, as there is no visible sign of water at the surface.

The priority was to isolate which section of pipework was responsible and then pinpoint the precise leak location without unnecessary excavation.

Key Symptom
The external water meter passed water continuously at 1 litre per minute with no water in use inside the property, and continued flowing after the internal stopcock was isolated, confirming the leak was on the underground section between the meter and the stopcock.

Methods Used

acoustic leak detection equipment probing side-of-property pathway during the survey

The investigation began with sectional isolation, closing the internal stopcock in the kitchen to determine whether the leak was inside or outside the building. With the meter continuing to flow after isolation, the leak was confirmed on the underground supply between the meter and the stopcock.

Tracer gas was then introduced into the pipework, and acoustic listening equipment was used to track the gas escaping at the defect point. This located the leak beneath a pathway at the side of the property.

In water mains leak detection involving buried supplies, this combination of techniques allows precise location without speculative digging.

Sectional Isolation. Closing the internal stopcock confirmed the leak was on the underground section between the external meter and the property, not on internal pipework.

Tracer Gas. Gas was introduced into the underground pipework and used to trace the escape point to the defective transition joint beneath the side pathway.

Acoustic Listening. Listening equipment detected the sound and signal of escaping tracer gas at the leak location, allowing the excavation point to be precisely marked.

Pressure Testing. Pressure conditions on the pipework were assessed as part of confirming the leak characteristics during the investigation.

Investigation Process

  1. 1
    Meter flow confirmed

    On arrival, the external water meter at the entrance to the driveway was inspected and found to be passing water at a steady rate of 1 litre per minute with no water in use at the property.

  2. 2
    Internal stopcock isolated

    The internal stopcock, located in the kitchen at the rear of the property, was closed. The meter continued to flow, confirming the leak was on the underground pipework between the meter and the stopcock.

  3. 3
    Tracer gas introduced

    Tracer gas was introduced into the underground pipework to allow the leak point to be located without excavating the full run.

  4. 4
    Leak located beneath side pathway

    Using acoustic listening equipment to track the escaping gas, the leak was traced to a point beneath a pathway at the side of the property, where leaking noise could also be heard.

  5. 5
    Area excavated and leak identified

    The pathway was opened up at the identified location, exposing a transition joint where old pipework connected to new pipework — this joint was the source of the leak.

  6. 6
    Joint replaced and area reinstated

    The defective transition joint was removed, new seals were installed, and the excavated area was backfilled.

  7. 7
    Customer advised on pipework

    The customer was informed that the underground black poly pipe was an unusual size, which is relevant for any future work on the supply.

Result & Outcome

leak located at transition joint on black poly underground mains pipe exposed beneath pathway

The customer was also advised that the underground black poly supply pipe was an unusual size. This is worth noting for any future maintenance or repair work on the supply, as standard fittings may not be suitable.

Completed by Vincent Morgan, leak detection engineer at ADI Leak Detection.