Internal Cold Mains Leak Detection in Lewes

A cold mains leak in Lewes was located using visual inspection, a damp meter, acoustic correlation, thermal imaging, and pressure testing, with water mains leak detection confirming the failed pipe section beneath the floor at the junction of the WC and hallway before any boards were lifted. The work was carried out by engineer Mark Pavitt.

Leak Located Lewes 0800 731 3843
CIPHE CIPHE accredited
WIAPS WIAPS member
£5m public liability insurance

THE UK'S #1 LEAK DETECTION SPECIALISTS

Facts

LocationLewes
CountyEast Sussex
Leak TypeWater Mains Leak Detection
Property TypeResidential property
Detection MethodVisual Inspection, Damp Meter, Acoustic Correlation, Thermal Imaging, Pressure Testing
OutcomeFailed 15mm mains supply located and renewed under closet WC floor.

Symptoms

water-damaged skirting board base with staining at floor level before leak detection works

At a property in BN10, leak evidence had begun rising through the floor of a closet WC. Visible damage was present on walls, woodwork, and flooring across both the closet WC and the adjoining hallway, indicating a subsurface leak that had been active long enough to cause widespread saturation.

Because the damage was spread across two areas with no obvious above-floor source, internal leak detection was required to trace the origin before any repair work could begin. The mains supply had already been isolated prior to arrival, meaning the active leak source needed to be confirmed through methodical testing rather than surface observation alone.

The extent of the damp and structural damage to the flooring and woodwork pointed to a pressurised supply leak rather than a drainage issue, making it necessary to reinstate the mains supply under controlled conditions to confirm the source and location.

Key Symptom
Water rising through the tiled floor between the hallway and closet WC when the previously isolated mains supply was reinstated.

Methods Used

thermal imaging camera screen showing heat mass around pipework beneath floor during leak detection

The investigation began with a visual inspection and damp meter survey across all affected areas in the closet WC and hallway, establishing the extent and distribution of moisture damage. With maximum damp readings recorded on floors, walls, and woodwork in both spaces, the mains supply was carefully reinstated to allow active observation — water was immediately seen rising through the tiled floor at the junction of the two areas.

Acoustic testing confirmed an irregularity from that same location, and thermal imaging identified a thermal mass consistent with pressurised water pooling around localised heating pipework beneath the floor. This combination of methods, standard practice in internal leak detection, narrowed the source to a specific section of 15mm copper mains supply running beneath the central heating pipework, allowing tiles and screed to be removed with precision.

Visual Inspection. Used on arrival to identify and document the distribution of leak damage — staining, saturation, and deterioration — across walls, woodwork, and flooring in the closet WC and hallway.

Damp Meter. Deployed throughout both affected areas to measure moisture levels, returning maximum readings on the flooring, walls, and woodwork in the WC and hallway and confirming the extent of water ingress.

Acoustic Correlation. Applied after the mains supply was reinstated to detect acoustic irregularities, confirming a signal consistent with a pressurised pipe failure at the junction of the hallway and closet WC floor.

Thermal Imaging. Used to identify a thermal mass caused by water from the failed mains supply pooling around the localised central heating pipework beneath the floor, corroborating the acoustic findings.

Pressure Testing. Carried out on completion of the repair to verify the renewed section of mains supply was sound and that no further leaks were present.

Investigation Process

  1. 1
    Visual inspection on arrival

    The engineer visually inspected all affected areas, identifying leak damage — including staining and deterioration — on walls, woodwork, and flooring in both the closet WC and the hallway.

  2. 2
    Damp meter survey

    A damp meter test was carried out throughout both spaces. Maximum readings were recorded on the flooring, walls, and woodwork in the WC and hallway, confirming widespread moisture saturation.

  3. 3
    Mains supply reinstated

    The previously isolated mains supply was carefully reinstated. Water was immediately observed rising through the tiled floor at the junction of the hallway and closet WC, identifying the active leak zone.

  4. 4
    Acoustic test

    An acoustic test was carried out over the area. An irregularity was detected from the same location where water had been seen rising, consistent with a pressurised pipe failure beneath the floor.

  5. 5
    Thermal imaging

    Thermal imaging identified a thermal mass beneath the floor, caused by water from the failed mains supply pooling around localised central heating pipework in that area.

  6. 6
    Mains isolated, floor opened

    The mains supply was re-isolated and tiles and screed were removed to gain access. A failed 15mm copper mains supply was discovered running beneath the central heating pipework.

  7. 7
    Pipe section renewed

    The failed section of 15mm copper mains supply was renewed, with the replacement routed correctly beneath the central heating pipework.

  8. 8
    Completion test and customer advice

    The repair was pressure tested on completion and passed. The customer was advised to contact their insurance company to arrange professional drying and all remedial works under their trace and access policy.

Result & Outcome

fault identified at heavily corroded 15mm copper mains supply pipe removed from beneath floor — leak located at

The leak was traced to a failed section of 15mm copper mains supply running beneath the central heating pipework at the junction of the closet WC and hallway floor. The combination of acoustic correlation and thermal imaging allowed the precise area to be identified before any floor was lifted, keeping the access opening targeted and limited.

Once exposed, the failed pipe section was renewed and the repair was tested under pressure on completion — all passed. The internal leak detection process confirmed the leak source conclusively, meaning the customer now has a clear, documented record of the cause and location to support an insurance claim.

The customer was advised to send the engineer's report to their insurance company to arrange all remedial works, including professionally drying the affected areas. All works fall within the trace and access element of a standard buildings insurance policy.

Completed by Mark Pavitt, leak detection engineer at ADI Leak Detection.