Underground Water Mains Leak Detection in Gloucester
An underground water mains leak in Gloucester was located using pressure testing, tracer gas, acoustic correlation, visual inspection, a damp meter, and an endoscope camera, with water mains leak detection confirming the source at the front of the property. Found by engineer James Hunter.
Facts
| Location | Gloucester |
|---|---|
| County | Gloucestershire |
| Leak Type | Water Mains Leak Detection |
| Property Type | Residential property |
| Detection Method | Pressure Testing, Tracer Gas, Acoustic Correlation, Visual Inspection, Damp Meter, Endoscope Camera |
| Outcome | Underground mains leak located at front of property, excavated and repaired. |
Symptoms
With the stopcock closed and the sound still audible, the situation indicated a significant loss of water somewhere between the street main and the property. This is a common presentation in water mains leak detection work, where the leak lies underground and out of sight.
A large volume of water was also found sitting inside the property, adding urgency to locating and resolving the source.
Methods Used
Water mains leak detection on external supply pipes requires this combination of pressure testing and tracer gas when the pipe is buried and the leak cannot be seen. Each step on this job built on the last: meter observation confirmed the problem, pressure testing quantified it, and tracer gas with acoustic listening pinpointed it precisely enough to dig in one location.
Pressure Testing. Used to confirm there was an active pressure loss on the external mains pipework before introducing tracer gas.
Tracer Gas. Injected into the pipework and detected at the front of the property to identify the precise location of the underground leak.
Acoustic Correlation. Used to listen directly to the pipe at the front of the property, confirming the audible leak signal at the identified location.
Visual Inspection. The water meter was observed spinning continuously with the stopcock closed, providing the primary confirmation of an external mains leak.
Damp Meter. Used to assess the extent of water found sitting inside the property following the leak.
Endoscope Camera. Available on site to assist with inspection where access was limited.
Investigation Process
-
1Customer reports noise
The occupants noticed the continuous sound of running water from the bathroom with no appliance or tap in use.
-
2Plumber isolates stopcock
A plumber attended and isolated the internal stopcock; the noise persisted, indicating the leak was on the external mains supply.
-
3Meter observation on arrival
The internal stopcock was isolated and the water meter was observed spinning continuously and at high speed, confirming a significant active leak.
-
4Pressure test confirms leak
A pressure test was carried out on the pipework and confirmed there was a measurable loss, consistent with an active underground leak.
-
5Tracer gas introduced
Tracer gas was added to the pipework and detection was carried out at the front of the property, returning a strong positive reading.
-
6Acoustic listening confirms location
Acoustic equipment was used on the pipe at the front of the property, and the leak could be clearly heard, pinpointing the position.
-
7Customer agrees to excavation and repair
The customer agreed to proceed with digging out the identified location to carry out the repair.
-
8Excavation and leak found
The ground was dug out and a corroded coupling — previously buried underground — was found to have completely failed at the identified location.
-
9Repair completed and re-tested
The failed coupling and surrounding pipe were removed and replaced with new fittings and copper pipe; a pressure test confirmed no further leaks on the external mains.
-
10Customer witnesses findings
The customer was present throughout the excavation and repair and witnessed the corroded coupling and the completed work.
Result & Outcome
Excavation at the front of the property revealed a coupling that had been installed underground and had completely corroded away, causing the continuous loss of water. The corroded coupling and the affected section of pipe were removed. Two new 20 mil couplings, reducing kits to 15 mil copper, and new copper pipe were installed to complete the repair. A pressure test carried out after the repair confirmed there were no further leaks on the external mains.