Central Heating Leak Detection in Cricklade

A central heating leak in Cricklade was located using sectional isolation, tracer gas, and an endoscope camera to confirm the exact leak point within a wall void, completing central heating leak detection without unnecessary opening up. Found by engineer Richard Poberezniuk.

Leak Located Cricklade 0800 731 3843
CIPHE CIPHE accredited
WIAPS WIAPS member
£5m public liability insurance

THE UK'S #1 LEAK DETECTION SPECIALISTS

Facts

LocationCricklade
CountyWiltshire
Leak TypeCentral Heating Leak Detection
Property TypeResidential property
Detection MethodPressure Testing, Tracer Gas, Endoscope Camera, Sectional Isolation
OutcomeRedundant pipe behind kitchen hob unit found leaking and capped.

Symptoms

tracer gas cylinder and pressure gauges connected to heating system in cloakroom during leak detection

Central heating leak detection was clearly needed, but pinpointing the source was not straightforward. The system included both underfloor heating circuits and a radiator circuit, meaning the leak could have been anywhere across a relatively complex layout.

Systematic isolation was required before any trace work could begin.

Key Symptom
The heating system pressure dropped from 1 bar to zero within ten minutes of being refilled.

Methods Used

handheld tracer gas detector unit in carry case during leak detection survey

Endoscope investigations were carried out at low level in the wall adjacent to the hob, where a leaking redundant heating pipe was identified. A section of wall was removed to allow further endoscope work, which indicated the actual leak point was behind the hob unit itself.

Following agreement with the customer, the hob unit area was exposed to access the pipe. This approach — methodical isolation followed by tracer gas and camera work — is standard practice in central heating leak detection where the leak cannot be located by pressure testing alone.

Pressure Testing. Used to confirm the overall system leak, and then applied to each underfloor circuit individually to eliminate them as the source before focusing on the radiator circuit.

Tracer Gas. Injected into the drained radiator circuit; produced a high reading in the kitchen and an audible bubbling noise that directed investigation to the wall adjacent to the hob.

Endoscope Camera. Deployed at low level in the kitchen wall to visually identify the leaking redundant pipe, and used again after partial wall removal to confirm the leak was positioned behind the hob unit.

Sectional Isolation. Applied to each underfloor heating circuit in turn to systematically eliminate them and confirm the leak was isolated to the radiator circuit.

Investigation Process

  1. 1
    System refilled and pressure loss confirmed

    The heating system was refilled to 1 bar. Pressure dropped to zero within ten minutes, confirming an active leak.

  2. 2
    Underfloor circuit #1 isolated and tested

    The first underfloor heating circuit was isolated and a separate pressure test carried out. The result was the same — pressure dropped to zero within ten minutes.

  3. 3
    Underfloor circuit #2 isolated and tested

    The second underfloor heating circuit was isolated and pressure tested with the same outcome, eliminating both underfloor circuits as the source of the leak.

  4. 4
    Radiator circuit drained and tracer gas applied

    With both underfloor circuits ruled out, the radiator circuit was drained and tracer gas investigations were carried out. A high gas reading was detected in the kitchen and a bubbling noise could be heard.

  5. 5
    Endoscope investigation in kitchen wall

    An endoscope camera was used at low level in the wall adjacent to the hob. A leaking redundant heating pipe was identified within the wall void.

  6. 6
    Wall opened and further endoscope work carried out

    A section of the wall was cut away to allow further endoscope investigation, which indicated the actual leak point was behind the hob unit.

  7. 7
    Area behind hob exposed

    Following discussion with the customer, further exposure was agreed to access the leaking 15mm copper pipe located behind the hob unit.

  8. 8
    Leaking pipe identified and cause established

    The 15mm copper pipe was found to be in contact with a sharp stone, which had been cutting into the pipe wall. The stone was removed.

  9. 9
    Pipe cut and capped

    The leaking redundant section of 15mm copper pipe was cut short and capped off to seal the circuit.

  10. 10
    Pressure test passed and system refilled

    A pressure test at 2 bar held for 20 minutes with no drop, confirming the repair. The heating system was refilled and six radiators were vented.

Result & Outcome

removed section of 15mm copper pipe showing corrosion hole after repair completed

For central heating leak detection jobs of this type — where the system spans multiple circuits and the leak is concealed within a wall void — systematic isolation and tracer gas work are essential to avoid unnecessary exposure. In this case, the combination of sectional isolation, tracer gas, and endoscope camera work meant the exact leak point was confirmed before any significant opening up was agreed with the customer.

Completed by Richard Poberezniuk, leak detection engineer at ADI Leak Detection.

Suspect a leak at your property?

ADI Leak Detection specialists investigate leaks like this across the UK every day. No find, no fee terms apply on qualifying jobs.