Internal Cold Mains Leak Detection in Kilmarnock
An internal cold mains leak in Kilmarnock was located using pressure testing, thermal imaging, a damp meter, an endoscope camera, and acoustic correlation, completing water mains leak detection that also revealed deteriorating bathroom pipework and waste pipes in need of urgent upgrading. Found by engineer Hamaad Janjua.
Facts
| Location | Kilmarnock |
|---|---|
| County | Ayrshire |
| Leak Type | Water Mains Leak Detection |
| Property Type | Residential property |
| Detection Method | Pressure Testing, Thermal Imaging, Damp Meter, Endoscope Camera, Acoustic Correlation |
| Outcome | Hairline crack in copper pipe beneath bath, repaired. |
Symptoms
A two-storey property in KA17 was experiencing a leak that was making its presence known through the ceiling of the downstairs hallway. The source was unclear, and the upstairs occupant had already removed a sink and lifted a floorboard in an attempt to trace the origin — without success.
With the cause still unidentified, professional internal leak detection was called in.
Methods Used
From that point, moisture meter readings were taken beneath the bath and returned wet results, consistent with an active leak in that area. An endoscope camera was used to inspect cavities without further unnecessary lifting of floor coverings.
Thermal imaging was also deployed and identified a wet patch. With the area confirmed, several floorboards were lifted with the customer's permission, giving direct access and enabling a positive identification of the leak.
Internal leak detection carried out in this way — combining non-invasive scanning with targeted physical access — keeps disruption to a minimum while establishing the exact cause.
Pressure Testing. Confirmed a failure on the hot supply pipe while all other circuits, including cold mains and central heating, held pressure — directing the investigation to a specific system.
Thermal Imaging. Identified a wet patch in the floor area beneath the bathroom, corroborating the moisture meter findings and helping confirm the zone for floorboard access.
Damp Meter. Returned wet readings beneath the bath, indicating active moisture consistent with a leak directly in that area.
Endoscope Camera. Inspected the cavity beneath the bath and confirmed visible moisture, reducing the need for speculative lifting of floor coverings.
Acoustic Correlation. Used as part of the broader detection process to assist in ruling out other potential leak sources within the pipework.
Investigation Process
-
1Initial Assessment
The engineer attended the property in KA17 and reviewed the situation: a leak presenting in the downstairs hallway with no confirmed source, and prior attempts by the customer to locate it having proved unsuccessful.
-
2Central Heating Discounted
The customer confirmed no pressure loss on the central heating system, so that circuit was set aside and testing focused on the hot and cold water supplies.
-
3Pressure Testing Carried Out
Pressure testing was completed across the pipework. The hot supply pipe failed the test while all other circuits passed, identifying the hot supply as the source system.
-
4Moisture Meter Readings Taken
Damp meter readings were taken beneath the bath and returned wet results, pointing to an active leak in that specific area of the bathroom floor.
-
5Endoscope Camera Inspection
An endoscope camera was introduced into the cavity beneath the bath and confirmed visible moisture, consistent with a leak in close proximity.
-
6Thermal Imaging Deployed
Thermal imaging identified a wet patch in the same zone, providing further corroboration that the leak was localised beneath the bath area.
-
7Floorboards Lifted
With the customer's permission, several floorboards were lifted to gain direct access to the pipework, allowing the engineer to positively identify the cause.
-
8Leak Source Identified
A hairline crack in a copper pipe was found beneath the bath — the definitive source of the leak affecting the downstairs hallway.
-
9Repair Carried Out
The cracked section of pipe was cut back, new fittings were installed, and an isolation valve was added to the cold mains pipe.
-
10Retest Completed
A retest was carried out following the repair to confirm the leak had been resolved and the pipework was holding pressure.
-
11Recommendations Made
The bathroom pipework and waste pipes were observed to be in poor condition with signs of corrosion, and the customer was advised to consider upgrading both as a priority.
Result & Outcome
Beyond the immediate repair, the engineer noted that the bathroom pipework and waste pipes are in poor condition and showing signs of corrosion. Upgrading both is strongly recommended to prevent further leaks developing from the same deteriorating infrastructure.