Internal Cold Mains Leak Detection in Kilmarnock

An internal cold mains leak in Kilmarnock was located using pressure testing, thermal imaging, a damp meter, an endoscope camera, and acoustic correlation, completing water mains leak detection that also revealed deteriorating bathroom pipework and waste pipes in need of urgent upgrading. Found by engineer Hamaad Janjua.

Leak Located Kilmarnock 0800 731 3843
CIPHE CIPHE accredited
WIAPS WIAPS member
£5m public liability insurance

THE UK'S #1 LEAK DETECTION SPECIALISTS

Facts

LocationKilmarnock
CountyAyrshire
Leak TypeWater Mains Leak Detection
Property TypeResidential property
Detection MethodPressure Testing, Thermal Imaging, Damp Meter, Endoscope Camera, Acoustic Correlation
OutcomeHairline crack in copper pipe beneath bath, repaired.

Symptoms

peeling and water-damaged hallway ceiling at initial inspection before leak detection works

A two-storey property in KA17 was experiencing a leak that was making its presence known through the ceiling of the downstairs hallway. The source was unclear, and the upstairs occupant had already removed a sink and lifted a floorboard in an attempt to trace the origin — without success.

With the cause still unidentified, professional internal leak detection was called in.

Key Symptom
The downstairs occupant was experiencing an active leak in the hallway ceiling, with no identifiable source despite the customer having already removed a sink and lifted floorboards.

Methods Used

moisture meter displaying reading of 999 wet beneath bathroom floor during leak detection

From that point, moisture meter readings were taken beneath the bath and returned wet results, consistent with an active leak in that area. An endoscope camera was used to inspect cavities without further unnecessary lifting of floor coverings.

Thermal imaging was also deployed and identified a wet patch. With the area confirmed, several floorboards were lifted with the customer's permission, giving direct access and enabling a positive identification of the leak.

Internal leak detection carried out in this way — combining non-invasive scanning with targeted physical access — keeps disruption to a minimum while establishing the exact cause.

Pressure Testing. Confirmed a failure on the hot supply pipe while all other circuits, including cold mains and central heating, held pressure — directing the investigation to a specific system.

Thermal Imaging. Identified a wet patch in the floor area beneath the bathroom, corroborating the moisture meter findings and helping confirm the zone for floorboard access.

Damp Meter. Returned wet readings beneath the bath, indicating active moisture consistent with a leak directly in that area.

Endoscope Camera. Inspected the cavity beneath the bath and confirmed visible moisture, reducing the need for speculative lifting of floor coverings.

Acoustic Correlation. Used as part of the broader detection process to assist in ruling out other potential leak sources within the pipework.

Investigation Process

  1. 1
    Initial Assessment

    The engineer attended the property in KA17 and reviewed the situation: a leak presenting in the downstairs hallway with no confirmed source, and prior attempts by the customer to locate it having proved unsuccessful.

  2. 2
    Central Heating Discounted

    The customer confirmed no pressure loss on the central heating system, so that circuit was set aside and testing focused on the hot and cold water supplies.

  3. 3
    Pressure Testing Carried Out

    Pressure testing was completed across the pipework. The hot supply pipe failed the test while all other circuits passed, identifying the hot supply as the source system.

  4. 4
    Moisture Meter Readings Taken

    Damp meter readings were taken beneath the bath and returned wet results, pointing to an active leak in that specific area of the bathroom floor.

  5. 5
    Endoscope Camera Inspection

    An endoscope camera was introduced into the cavity beneath the bath and confirmed visible moisture, consistent with a leak in close proximity.

  6. 6
    Thermal Imaging Deployed

    Thermal imaging identified a wet patch in the same zone, providing further corroboration that the leak was localised beneath the bath area.

  7. 7
    Floorboards Lifted

    With the customer's permission, several floorboards were lifted to gain direct access to the pipework, allowing the engineer to positively identify the cause.

  8. 8
    Leak Source Identified

    A hairline crack in a copper pipe was found beneath the bath — the definitive source of the leak affecting the downstairs hallway.

  9. 9
    Repair Carried Out

    The cracked section of pipe was cut back, new fittings were installed, and an isolation valve was added to the cold mains pipe.

  10. 10
    Retest Completed

    A retest was carried out following the repair to confirm the leak had been resolved and the pipework was holding pressure.

  11. 11
    Recommendations Made

    The bathroom pipework and waste pipes were observed to be in poor condition with signs of corrosion, and the customer was advised to consider upgrading both as a priority.

Result & Outcome

bathroom with floorboard removed and exposed pipework before leak detection works

Beyond the immediate repair, the engineer noted that the bathroom pipework and waste pipes are in poor condition and showing signs of corrosion. Upgrading both is strongly recommended to prevent further leaks developing from the same deteriorating infrastructure.

Completed by Hamaad Janjua, leak detection engineer at ADI Leak Detection.